January 14, 2016

Download

State of Physical Access Trend Report 2024

Xtralis VESDA Aspirating Smoke Detectors Protect New Abu Dhabi Airport Terminal

xtralis abu dhabiXtralis VESDA VLS aspirating smoke detectors will provide fire prevention at the new Abu Dhabi International Airport Midfield Terminal Building (MTB), scheduled to open in 2017.

The MTB will be the largest in the Emirate of Abu Dhabi, and one of the region’s most architecturally impressive structures. Xtralis VESDA & VESDA-E aspirating smoke detectors (ASD) now protect many of the United Arab Emirates super structures, including the Burj Khalifa, Emirates Palace Hotel, and Dubai & Abu Dhabi International Airports. Xtralis VESDA brand is the world’s most dominant aspirating smoke detector, with greater than 65% ASD worldwide market share, according to estimates from IHS Technology.

The new Midfield Terminal Complex (MTC) will have 700,000 sq-m of internal space for a passenger terminal (MTB), cargo facility, and restaurant and retail space. The size of the MTC is so impressive that it will be visible from 1.5 km away.

The facility can accommodate 8,500 passengers per hour and up to 30 million per year. The central space of the terminal building could hold three full-sized football (soccer) pitches and features a ceiling 52 m tall at its highest point, taller than the Emirates Palace and will include 28,000 sq-m of retail outlets and restaurants.

Chief among the challenges with protecting the MTB was the massive open space where smoke will be diluted, an effect compounded by air-conditioning systems. VESDA’s early and reliable detection combined with the VLS capability of monitoring the protected space by sectors were key factors that resulted in the selection of the Xtralis solution.

Additionally, temperatures in the terminal could range from hot to cold, depending on the weather, and VESDA was the only detector that could ensure early and reliable detection under these conditions. Xtralis provides comprehensive safety and security solutions for airports, including smoke and gas detection, perimeter security, and intrusion detection. To learn more, click here.

The VESDA LaserScanner (VLS) is similar to the VESDA LaserPlus (VLP) detector, but also includes a valve mechanism in the inlet manifold and software to control the airflow from the four sectors (pipes). This configuration enables a single zone to be divided into four separate sectors, for example, distinguishing between separate voids within a room.

The VLS draws air from all sectors in use. If the smoke level reaches the Adaptive Scan Threshold, the VLS performs a Fast Scan of each pipe to identify which pipe is carrying smoke.

If more than one pipe is transporting smoke, the sector with the highest smoke concentration is scanned first. Once Fast Scan is completed and the sector with the highest smoke concentration is identified, the VLS continues to closely monitor all four sectors (pipes) to monitor fire growth and maintain full protection of the area.

There are four alarm levels (Alert, Action, Fire 1 and Fire 2) for each sector (pipe) and the sensitivity for each alarm level can be set to ensure the optimum alarm thresholds are applied for each sector. Click here to learn more about the entire line of VESDA detectors.

2023 Fire Safety eBook – Grab your free copy!

Download the Fire Safety in 2023 eBook, keeping you up to date with the biggest news and prosecution stories from around the industry. Chapters include important updates such as the Fire Safety (England) Regulations 2022 and an overview of the new British Standard for the digital management of fire safety information.

Plus, we explore the growing risks of lithium-ion battery fires and hear from experts in disability evacuation and social housing.

FireSafetyeBook-CoverPage-23

Related Topics

Subscribe
Notify of
guest
0 Comments
Oldest
Newest Most Voted
Inline Feedbacks
View all comments