Claire is Director of Clarity Safety Solutions Ltd., an Oban-based health and safety consultancy. She has more than 17 years of health and safety experience advising organisations and is a Chartered Member of the Institution of Occupational Safety and Health, an OSHCR registered consultant, and an IFE registered life safety assessor. Since attempting to leave the rat race in 2008, and moving to the West Coast of Scotland, Claire has written hundreds of articles, reports, policies, papers, newsletters, and training courses. Nevertheless, she continues to help clients directly with their health, safety, and fire safety arrangements both within the UK and abroad.
July 11, 2013

Download

Whitepaper: Enhancing security, resilience and efficiency across a range of industries

Domestic Fire Alarm Standards Updated: What You Need to Know

Last month, we published an outline of changes to BS5839-1 relevant to nondomestic fire detection and alarm systems. On May 31, the British Standards Institute also updated its sibling standard: Fire detection and fire alarm systems for buildings, Part 6, code of practice for the design, installation, commissioning and maintenance of fire detection and fire alarm systems in domestic premises.

You may not have access to a copy of BS5839-6: 2013. If you’re wondering whether you need to buy it or whether to spend the money on a holiday (it’s not cheap), here’s a quick rundown of what’s covered.

What is it?
BS5839-6 is the standard to be adopted for any new or upgraded fire detection and fire alarm systems to be installed in domestic premises. The scope of the standard used to be focused on individual dwellings. In fact, the document was previously littered with the word “dwelling,” but in almost all instances, that word has been replaced by “premises.” The primary reason for this change is that the standard now covers sheltered housing premises, including the common parts.

Who should use it?
It’s quite a technical document, and it isn’t written for the lay person to interpret. It’s primarily aimed at architects, alarm system designers, installers, electricians, and other building professionals. Although it’s for domestic premises, many of which are exempt from fire risk assessment requirements, there’s value here for fire risk assessors who could be involved in assessments of communal areas in blocks of flats, sheltered housing, and houses of multiple occupation.

What has changed?
The new edition, which replaces BS5839-6: 2004, introduces a number of technical changes. With so many years between the versions, it’s no surprise that updates have been made throughout to cross-reference current standards and to remove outdated references. And even though it’s billed as a technical update (not a full review), there are some more significant changes.

As mentioned above, the inclusion of sheltered housing communal spaces and facilities has been a major source of additional advice within the document. A new clause (9.1.5) is dedicated to this topic and adds about two pages to the total. Also, there are tweaks and alterations throughout the standards to accommodate sheltered housing as a new subject. Detailed thought has gone into the arrangements that need to be made for automatic detection and the sounding of alarms. There are conflicting needs here:

  • Not getting residents to evacuate unless it’s really needed
  • Limiting the risk of false alarms
  • Ensuring that the alarm is heard by everyone, including the hard of hearing
  • Ensuring a rapid response from the fire and rescue service

New recommendations are included to ensure that, in sheltered housing, fire alarm signals transmitted to an alarm receiving centre via a social alarm system cannot be delayed by other alarm signals originating from the fire origin or elsewhere.

Addressable fire detection and fire alarm systems are recommended for sheltered housing, with connections between detectors within dwellings and common parts. Sounders or smoke alarms are recommended for the main bedroom of a sheltered flat or house to improve audibility.

Here are some more recommendations:

  • A smoke detector, rather than a heat detector, is now recommended for the principal habitable room(s) of a new premises. (This is a U turn from the 2004 standard, which was quite explicit in its advice that heat detectors should be used in these rooms to avoid false alarms.) Carbon monoxide fire detectors can be used as an alternative in the principal habitable room(s), though only heat detectors should be used in kitchens.
  • Table 1 has been slightly amended to change recommended categories of systems for different applications. For example, a Grade A system, rather than Grade B, is now expected for a four-storey house. (There’s no expectation to upgrade systems that complied with the previous standard.)
  • Due to an increase in plant and electrical equipment installed within loft spaces (e.g., due to solar power), there’s additional advice on the provision of detection in these areas, including siting to avoid adverse impact on performance from the roof shape or structural beams.
  • There’s new advice relating to systems in houses of multiple occupation, particularly in relation to power supply to alarms and detectors.
  • The standard also includes clearer advice on warning systems for those who are deaf or suffer hearing loss.
  • There is advice (also worth following) to check the particulars of alarm receiving centres. If you’re relying on third-party certification under BS5979 as proof of quality, you should check that the receipt of fire alarm signals is within the scope of that certification. It may not be, it seems.

Though the BSI states that this document isn’t the result of a full review, there are some significant and wide-ranging changes. If the standard is a key reference text for your business, it’s worth making sure you have the 2013 version.

2023 Fire Safety eBook – Grab your free copy!

Download the Fire Safety in 2023 eBook, keeping you up to date with the biggest news and prosecution stories from around the industry. Chapters include important updates such as the Fire Safety (England) Regulations 2022 and an overview of the new British Standard for the digital management of fire safety information.

Plus, we explore the growing risks of lithium-ion battery fires and hear from experts in disability evacuation and social housing.

FireSafetyeBook-CoverPage-23

Related Topics

Subscribe
Notify of
guest
8 Comments
Oldest
Newest Most Voted
Inline Feedbacks
View all comments
Tommy Lovell
Tommy Lovell
July 12, 2013 9:51 am

In part 6 what is ” a very large dwelling” as this makes a huge difference. For instance is a block of say thirty flats considered to be a very large building or do you consider each flat as a separate dwelling.
Tommy Lovell
[email protected]

Claire Rizos
Claire Rizos
July 12, 2013 11:21 am
Reply to  Tommy Lovell

Part 6 of BS5839 does not provide recommendations for fire alarm systems in communal parts of blocks of flats. Recommendations are however provided for common parts and communal facilities in sheltered housing unless, architecturally and in terms of facilities the premises are no different from general needs blocks of flats. As to the definition of ‘very large’ dwelling, this term is used in several places in the standard and usually explained in the context of the specific recommendation where it’s been used, e.g. ‘in a very large property such as a country house or mansion, and in most houses of multiple… Read more »

ITs_Hazel
ITs_Hazel
July 15, 2013 2:52 am
Reply to  Claire Rizos

I think this ambiguity can be addressed by providing estimates or approximations of actual values. By defining what “large” is can clear up a lot of concerns people have as it presently seems too subjective a term to use.

Tommy Lovell
Tommy Lovell
July 15, 2013 5:59 am
Reply to  Claire Rizos

Thank you very much for your reply and your comments are appreciated. However our problem is that we have been asked to install a system in a single, quite modern building which consists of thirty five normal flats which are rented to the general public. We would class this as a large building should BS5839 part 1 apply or part 6?
Tommy Lovell

Claire Rizos
Claire Rizos
July 15, 2013 7:41 am

BS 5839-6 applies to forms of domestic premises, including individual flats and maisonettes. It does not apply to the communal parts of blocks of flats or maisonettes. BS5839-1 provides recommendations for the planning, design, installation, commissioning and maintenance of fire detection and fire alarm systems in and around buildings, other than domestic premises. On the above basis you may need to use both in your scenario of a block of 35 flats. But note that for specific advice you would be well advised to read page 28/ 29 of ‘Fire Safety in Purpose Built Blocks of flats’ http://www.local.gov.uk/c/document_library/get_file?uuid=71e152a6-9e0a-4810-aee6-498167664f79&groupId=10171 which elaborates… Read more »

SunitaT
SunitaT
July 22, 2013 12:54 pm

, thanks for the post.  I think its always better if we place Fire alarms and smoke detectors in the middle of house so that it could detect fire and smoke easily and everyone could hear the sound of it. I am sure these standards will help improve the safey.

ITs_Hazel
ITs_Hazel
August 1, 2013 1:40 pm
Reply to  SunitaT

I’m definitely with Sunita on this. These updates make sense and I’m glad to hear of them, actually. Thanks for the very informative post, Claire!

gbrown
gbrown
August 5, 2013 3:48 am
Reply to  ITs_Hazel

I agree with you all . It is extremely important that we are having discussions and updates of improving our domestic fire alarm standards.